In my case i have 1 6kw solar but 9 6kwh golf battery system it will never get fully charged unless i choose so.
Backfeed breaker solar.
The backfeed generator breaker can t be closed while there is main power on the panel and when there is a power failure it can only be closed after the main breaker is open.
The problem is the backfeeding only happens when battery is fully charged.
According to the manual backfeeding is a real grid tie system once the grid is off the backfeeding stops.
The nec allows adding a back feed breaker so that the current supply is up to 120 of the rating of the bus bar.
When setting up a generator to backfeed your house power can be pushed out through the main breaker to the transformer and cause unexpected high voltage.
As noted in sec.
Circuit requirements are outlined in part ii of this article.
From there you d land your inverter s output into a 50a breaker and your done.
We sometimes see people adding a 60 or 80 a breaker instead.
Energizing wiring systems far from your setup like this can damage your equipment and the appliances being powered as well as potential for electrocution to technicians repairing power lines.
If a 200 a busbar has a 200 a main breaker the code allows adding a up to a 40 a backfeed breaker.
The main purpose of the fuses and breakers are to protect the wiring.
Article 690 requirements apply to solar pv systems.
Nec705 12 b 2 3 b states that where there are two power sources the grid and the solar inverter the sum of their breakers cannot equal more than 120 of the busbar rating of the breaker box.
The transfer switch or interlocked backfeed breaker acts to prevent the connection of the generator while the main breaker for the panel is closed.
690 10 e plug in type back fed circuit breakers connected to a stand alone inverter output in either stand alone or utility interactive systems shall be secured in accordance with 408 36 d.